Siemens SINAMICS S120 Equipment Manual page 195

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Internal air cooling
Rated power
DC link capacitance
Maximum permissible DC link
capacitance
Power factor
Circuit-breaker type designation
(status 06/2007)
Rated current
Short-circuit current rating SCCR at
400 V
AC
Circuit-breaker type designation
(status 07/2007 and later)
Rated current
Short-circuit current rating SCCR at
400 V
AC
Short-circuit current rating SCCR at
480 V
AC
Short-circuit current rating SCCR at
600 V
AC
Circuit-breaker type designation
UL489/CSA C22.2 No. 5-02
Rated current
Rated short circuit current SCCR
UL safety fuse type AJT Class J
Rated current
Short-circuit current rating SCCR at
600 V
AC
Safety fuses NH
Rated current
Sound pressure level
Cooling air requirement
Rated voltage for rated data 380 V 3 AC
Weight
1) The specified values apply to 380 V
2) For an overview, see the power loss tables in Cabinet Design chapter.
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
6SL3131–
7TE21–6AAx
kW
16
μF
705
μF
20 000
cosϕ
1
3RV1031-
4FA10
A
28 ... 40
kA
50
3RV1042-
4FA10
A
28 ... 40
kA
100
kA
kA
To be added
A
kA
AJT35
A
35
kA
200
3NA3 814
A
35
dB(A)
<60
m
/h
56
3
kg
8.78
3.3 Active Line Modules with external air cooling
7TE23–6AAx
7TE25–5AAx
36
55
1 410
1 880
20 000
20 000
1
1
3RV1041-
3VL2712-
4LA10
3DC33-0AA0
70 ... 90
125
50
3RV1042-
3VL2112-
4LA10
3KN30-0AA0
70 ... 90
125
100
100
25
3VL2108-
3VL2112-
3KN30-0AA0
3KN30-0AA0
80
125
65
65
AJT80
AJT125
80
125
200
200
3NA3 824
3NA3 132
80
125
<65
<60
112
160
13.77
18.5
Line Modules Booksize
7TE25–5AA3
+ Active
Interface
Module
55
1 880
20 000
1
3VL2712-
3DC33-0AA0
125
3VL2112-
3KN30-0AA0
125
100
25
3VL2112-
3KN30-0AA0
125
65
AJT125
125
200
3NA3 132
125
<60
160
18.5
195

Advertisement

Table of Contents
loading

Table of Contents