Siemens SINAMICS S120 Equipment Manual page 259

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

NOTICE
Operation without the line reactor is not permissible.
CAUTION
The DC link side covers are supplied as standard with the components; they can also be
ordered separately, if required (order no.: 6SL3162-5AA00-0AA0).
If the Line Module is not disconnected from the network (e.g. via the main contactor or main
circuit-breaker), the DC link remains charged.
Note
The fans are power-up and power-down as a function of the heatsink temperature.
The fans start up at the heat-sink temperature specified in the power stack data (normally
56°C) and are switched off with a slight hysteresis when the heat-sink temperature
decreases again. The length of time it takes for the fans to stop once they have been
switched off depends on a number of factors (ambient temperature, output current, duty
cycle, etc.) and, therefore, cannot be determined directly.
The fans are not equipped with temperature-dependent speed control; Only the states on or
off exist.
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
3.6 Smart Line Modules (16 kW und 36 kW) with internal air cooling
WARNING
Line Modules Booksize
259