2.4

Basic Line Filter for Active Line Modules with line reactor

2.4
2.4.1

Description

The Basic Line Filters for Active Line Modules are designed for limiting the cable-borne
interference in accordance with the specifications of the EMC legislation.
The machine manufacturer must certify the machines that he plans to launch on the market
in accordance with the EU EMC Directive.
General conditions regarding Basic Line Filters and line reactors for Active Line Modules
The Basic Line Filters can be used in accordance with the following general conditions for
ensuring CE conformity with regard to cable-borne interference:
● The machine/system must only be used in industrial networks.
● No. of axes ≤12.
● Total cable lengths ≤150 m (motor cables, power supply cable between line filter and
The Basic Line Filters are only suitable for connection to TN systems; otherwise an
isolating transformer will be required.
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Line Module).
2.4 Basic Line Filter for Active Line Modules with line reactor
Line Connection Booksize