Siemens SINAMICS S120 Equipment Manual page 376

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules Booksize Compact
5.2 Safety information
The Motor Modules conduct a high leakage current. Because of the high leakage current of
the Motor Module, a permanent PE connection of the Motor Module or control cabinet is
required.
Other than that the following measures must be taken in accordance with EN 61800-5-1:
Either protective ground conductor cross-sections ≥ 10 mm
protective ground conductor of the same cross-section as the first one.
The DC link discharge voltage hazard warning in the local language must be attached to all
of the components.
A set of labels in 16 languages is supplied with the component.
A ventilation clearance of 80 mm above and below the components must be observed.
It is only permissible to establish connections to the DC link using the adapters that
SIEMENS has recommended (DC link adapter and DC link rectifier adapter).
CAUTION
The tightening torque of the DC link busbar screws (1.8 Nm, tolerance +30 %) must be
checked before commissioning. After transportation, the screws must be tightened.
If a 50 mm wide Motor Module or if a DC link component with the appropriate width (e.g.
Braking Module, Control Supply Module, Voltage Clamping Module) is located at the
lefthand end of the drive line-up, then the DC link bridge including all of the screws must be
removed. It is not permissible to insert the screws without a DC link bridge.
For all other power units and DC link components (e.g. Capacitor Module) that are wider
than 50 mm, it is neither permissible to move the DC link bridge to the left nor remove it.
If this is not carefully observed, this can result in damage and accidents.
376
DANGER
DANGER
WARNING
DANGER
DANGER
Cu or installation of a second
2
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6