Line Modules Booksize
3.7 Smart Line Modules Booksize Compact
3.7.7

Technical data

Table 3-59
Technical data for Smart Line Modules in Booksize Compact format
Smart Line Module Booksize Compact
Rated power
Infeed:
Rated power (S1)
1)
S6 infeed
Power rating (S6-40%)
Peak power rating
1)
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
Input current:
Rated current at 380 V
AC
at 480 V
/528 V
AC
AC
at 480 V; S6 duty (40 %)
Peak current
DC link current:
At 600 V DC
at S6 duty (40 %)
peak current
DC link busbar current carrying capacity
24 V busbar current carrying capacity
Current consumption of electronics for internal air
cooling
Current consumption of electronics for cold-plate
cooling
Total power loss internal air cooling
(including electronic losses)
Power loss distribution for cold plate (including
electronics losses)
Internal
External
Max. ambient temperature without derating
Max. ambient temperature with derating
DC link capacitance
Maximum permissible DC link capacitance
Power factor
290
1)
2)
6SL3430–
6TE21-6AAx
kW
16
kW (Pn)
16
kW (Ps6)
21
kW (Pmax)
35
kW
16
kW
35
V
380 3 AC -10 % (-15 % < 1 min) up to 480 3 AC +10 %
AC
Hz
47 to 63
V
24 (20.4 - 28.8)
DC
V
510 – 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
26
AC
A
21/19
AC
A
35
AC
A
59
AC
A
27
DC
A
35
DC
A
59
DC
A
100
DC
A
20
DC
A
1.1
DC
A
0.9
DC
W
191.4
W
56.6
130
°C
40
°C
55
μF
705
μF
6000
cos ϕ
0.98
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6