Siemens Sinamics S120 Manual page 193

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Article number
Max. cable length
(total of all motor cables and DC link)
- Shielded
- Unshielded
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Recommended fuse
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
Valid for a 5s duty cycle (overload duration) and a duty cycle duration of 300s based on the rated DC-link current.
1)
Valid for a 5s duty cycle (overload duration) and a duty cycle duration of 300s based on the rated infeed/regenerative
2)
feedback current.
The specified power loss is the maximum value at 100% utilization level. The value in normal operation is lower.
3)
This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant proper-
4)
ties".
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
5)
When using fuses connected in parallel in each phase, if one fuse ruptures, then all of the fuses must be replaced.
6)
Minimum current required for reliable triggering of the protective devices.
7)
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3335–
m
m
mm
mm
mm
kg
A
A
7)
7TG41–3AA3 7TG41-6AA3
2250
2250
3375
3375
IP00
IP00
295
295
1516
1516
545
545
JXL
JXL
220
230
3NE1438-2
3NE1436-2
5)
2
3
6)
6)
800
630
3
3
20000
24000
Line Modules
5.3 Active Line Modules
193