Drive Parameter
85.20 MB open by
direct online
97.40 Output choke
inductance
97.46 SBU current
control gain
Set parameters for inductor bypass contactor.
If inductor bypass contactor is used as a c-plus option, below parameters need to be
set. Inductor bypass contactor can only be used when MB and MSS are steady signal
control (one coil control).
setting
Description
Disabled
If it's enabled, 1 →0 of MB DOL command (BCU DI4, or 85.01 SBU
control and monitoring CW bit 2) will open MB. For Multi motor,
(example)
disabled is necessary.
1.48mH
Define the inductance of the output choke.
(example)
0.25
Gain for current close loop control. The value needs to be confirmed
during commissioning.
(example)
Option 113