ABB ACS580MV Commissioning Manual page 71

200kw to 6300 kw,3.3kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

b. Start/Stop/Direction, in parameter group 20.
c. Start/Stop mode, in parameter group 21.
d. Speed reference ramp, in parameter group 23.
e. Frequency reference chain, in parameter group 28.
f. Protection, in parameter group 34.
Note: Generally, the protection parameters need to be set as default, do not modify
unless receive the permission from MV Drives Supportline.
Motor thermal protection, if need (motor temperature, cable temperature, motor
cooling fan), in parameter group 35.
Energy efficiency, in parameter group 45.
Monitoring and scaling, in parameter group 46.
Internal fieldbus settings, in parameter group 54.
Note: Only save and set, active default setting IO controller.
Local control disable, in parameter group 81.
Note: Including the logic test, refer to the DriveStartup.
MCB available / MCB ON prevention / MCB external protection monitoring, in
parameter group 82.
Note: Including the logic test, refer to the DriveStartup.
For particular parameter description refer to the
(3BHS811381).
Standard Commissioning Process 71
ACS580MV Firmware Manual