10. Safety devices
Type of
protection
Fuse (Main)
Protector (Inv)
Circuit protection
Protector (Fan motor)
Fuse (Varistor)
Over current
protection
Discharge pipe
temperature
Compressor
protection
protector
Compressor
temperature
protection
High pressure protection
Low pressure protection
Protection form
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
- (03-22) -
Model
AOU72RLAVL
AOU96RLAVL
AC 250 V, 10 A
AC 250 V, 80 A
DC 750 V, 10 A
AC 250 V, 3.15 A
248 °F (120 °C)
Compressor stop
185 °F (85 °C)
Compressor restart
266 °F (130 °C)
Compressor stop
194 °F (90 °C)
Compressor restart
580 psi (4.0 MPa)
Compressor stop
464 psi (3.2 MPa)
Compressor restart
7.25 psi (0.05 MPa)
Compressor stop
AOU120RLAVL