Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 509

Table of Contents

Advertisement

¢ Electrical wiring
*Connect SW2 only when it is used.
Connection to external contacts
Dry contact
SW1
SW2
COM
Terminal
External switch controller
¢ Dimensions
3-10. External switch controller (UTY-TEKX)
External input cable
External input
External switch controller
External contact SW 1
External contact SW 2
1-3/16 (30)
2-15/16 (75)
5-Ø1/4 (7)
11/16 (18)
Left view
Front view
- (05-171) -
Remote controller cable
Remote
controller cord
Open circuit voltage: 12 V ± 2 V
Short circuit current: ≤ 2 mA
Short circuit detection resistance (R on): ≤ 1 kΩ
Open circuit detection resistance (R off): ≥ 50 kΩ
2-3/8 (60)
Rear view
Remote
control
Indoor unit
Unit: in (mm)