Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 664

Table of Contents

Advertisement

LED105
Setting mode
code no.
Operation
2
1
mode selecting
method
2
2
Prohibited
2
3
Prohibited
2
4
Prohibited
2
5
Prohibited
2
6
Prohibited
2
7
Prohibited
Change of unit
2
8
(Temperature)
Change of unit
2
9
(Pressure)
Outdoor unit
3
0
capacity save
setting
3
1
Prohibited
Presence of
heater
selection
3
5
control using
outdoor
temperature
2-1. Setting on outdoor unit PCB
LED104
Setting function
code no.
Priority given to the first
0
0
command
Priority given to external
0
1
input of outdoor unit
Priority given to
0
2
administrative indoor
unit
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Celsius (°C)
0
1
Fahrenheit (°F)
0
0
MPa
0
1
psi
0
0
Level 1 (Stop)
0
1
Level 2
0
2
Level 3
0
3
Level 4
0
4
Level 5
0
0
Prohibited
0
1
Prohibited
0
0
Disabled
0
1
Enabled
- (07-64) -
Factory
Remarks
setting
Select the priority setting of the
operation mode.
Priority given to the first
command: Priority is given to
the operation mode which is
set first.
Priority given to external input
of outdoor unit: Priority is
given to the operation mode
which is set by the external
input terminal (CN132).
Priority given to administrative
indoor unit: Priority is given to
the operation mode of the
administrative indoor unit
which is set by the wired
remote controller.
Setting prohibited
Setting prohibited
Setting prohibited
Setting prohibited
Setting prohibited
Setting prohibited
The capacity limit in Energy saving
peak cut control operation can be
selected. With lowering the level,
the energy efficiency get higher
but the cooling or heating
performance gets lower.
Setting prohibited
For heater control switching,
setting of heater selection control
using outdoor temperature 1 and 2
is required. (Setting value of
function setting number 61 on
indoor unit: 03 or 04)
For details, refer to
output"
in Chapter 8. EXTERNAL
INPUT AND OUTPUT on page 08-
5.
"External
2. Function settings