Confirm whether satisfy the following calculation.
Total capacity of indoor units at design tempera-
ture ≥ compensated capacity of outdoor units
(A ≥ B)
System capacity = B
Calculate actual capacity of each indoor unit by
dividing system capacity proportionally.
Confirm whether satisfy the following calculation.
Actual capacity of indoor unit ≥ heat load
[▼▼▼]
System capacity = A
Actual capacity of indoor unit = capacity of in-
door unit at design temperature
1-2. Indoor unit and outdoor unit selection procedure
End
End
If A is lower than B, go to step marked [▼▼▼].
Refer to
"Capacity calculation method"
02-4.
If actual capacity of indoor unit is lower than
heat load, change to larger capacity of outdoor
units and return to step marked [▲▲].
If actual capacity of indoor unit is greater than
heat load, procedure is completing.
- (02-3) -
on page
1. Model selection and capacity calculation