Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 156

Table of Contents

Advertisement

¢ Installation space requirement
H1
119 (3,000) or more
AUUB18-30TLAV2
AUUB36-48TLAV2
Be sure to make function setting with the remote controller according to the installed ceiling height.
Ceiling height
Standard
High ceiling
 Installation notices
• When installing the indoor unit, be careful about the maintenance space.
• To set "3-direction", Air outlet shutter plate (option) must be installed, and the "outlet-direction"
need to be switched to "3-way" by the remote controller.
• In 3-way outlet mode, changing of ceiling height setting by function setting 20 is prohibited. (Ceil-
ing height setting [function setting 20] is allowed to be changed only in 4-way outlet mode.)
• Use the Insulation kit for high humidity (option), when the condition under the roof is over 80% in
humidity and over 86°F (30°C) in temperature. Otherwise, there is a risk of condensation on the
ceiling.
4-2. Circular flow cassette type
Strong and durable ceiling
71 (1,800) to H2
40 (1,000) or more
Floor
Model name
H2: The maximum height from floor to ceiling
AUUB18-30TLAV2
4 directions
Obstruction
Model name
118 (3,000)
138 (3,500)
4 (100) or more
3 directions
Piping position
- (04-32) -
Unit: in (mm)
60 (1,500) or more
H1: Attic height
11 (256) or more
12 (298) or more
AUUB36-48TLAV2
126 (3,200)
166 (4,200)
4. Dimensions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents