Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 697

Table of Contents

Advertisement

Function
Function
number
Cool air
temperature
30
trigger
Heat air
temperature
31
trigger
Auto restart
40
Cool-air
43
prevention
External
46
control
Error report
47
target
Fan setting
when
cooling
49
thermostat
OFF
2-9. Function details
Factory
Setting number
setting
00
Standard
01
Adjust (1)
02
Adjust (2)
00
Standard
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
00
Enable
01
Disable
00
Super low
Follow the setting
01
on the remote
controller
00
Start/Stop
01
Emergency stop
02
Forced stop
00
All
Display only on
01
central remote
control
Follow the setting
00
on the remote
controller
01
Stop
Adjusts the cool air trigger temperature.
To make the trigger temperature lower than the
standard temperature, use setting "01".
To make the trigger temperature higher than the
standard temperature, use setting "02".
Adjusts the heat air trigger temperature.
To make the trigger temperature 6 degrees C lower
than the standard temperature, use setting "01".
To make the trigger temperature 4 degrees C lower
than the standard temperature, use setting "02".
To make the trigger temperature higher than the
standard temperature, use setting "03".
Enables or disables automatic system restart after a
power outage.
NOTE: Auto restart is an emergency function such
as for power failure etc. Do not start and
stop the indoor unit by this function in
normal operation.
Be sure to operate by the control unit,
converter or external input device.
Restrains the cold airflow with making the airflow
lower when starting heating operation. To correspond
to the ventilation, set to "01".
Allows an external controller to start or stop the
system, or to perform an emergency stop, or to
perform a forced stop.
If an emergency stop is performed from an
external controller, same refrigerant system will
be disabled.
If forced stop is set, indoor unit stops by the input
to the external input terminals, and Start/Stop by
a remote controller is restricted.
Changes the target for reporting errors. Errors can
either be reported in all locations, or only on the wired
remote.
When set "00", indoor unit is continued operation
based upon central remote controller or
individual controller set.
Once indoor unit received signal from external
controller, indoor unit changed fan mode forcibly.
When set "01", indoor unit is continued operation
based upon central remote controller or
individual controller set.
Once indoor unit received signal from external
controller, indoor unit stop forcibly.
Connection of the wired remote controller (2-wire
type or 3-wire type) and switching its thermistor
are necessary.
- (07-97) -