Table 6-4 Alarm Action And Alarm Responses - Motorola iDEN Site Controller System Manual

Gen 3
Table of Contents

Advertisement

Gen 3 Site Controller System Manual
68P80801E30-A 5/1/2002
The tower top amplifier response (codes 228, 232, and 236) to the
Note:
display eas command is only returned on systems containing a
cavity combining RF Distribution System.
To verify a particular alarm, perform the proper action to trigger it.
2.
For example, the following describes this verification.
Open the site entry door.
2.1
Type: display eas
2.2
The status of the Site Entry alarm (code 219) changes to the
alarm state.
Close the site door.
2.3
Type: display eas
2.4
The Site Entry alarm (code 219) returns the O.K. condition.
Verify other alarms for proper wiring by triggering them as described
3.
above.
Some actions trigger more than one alarm. For instance, switching off the
main breaker to the Controller. Other alarms are site-specific, and may or
may not be wired. Site-specific alarms are generally more difficult to trigger
manually.
The alarm actions listed below do not remove power from the controller.
Removing controller power disrupts the testing procedure.
A list of alarms and actions required to trigger each are given in Table 6-4.
Table 6-4
Alarm action and alarm responses
If you do this . . .
Open site entry door
Set off smoke alarm
Trip thermostat high point
Trip thermostat low point
Switch off the EAS breaker
Switch off the RFS1 breaker of RFC1
Chapter 6 System Testing
EAS/EAS2 Alarm Checkout
Then this alarm triggers . . .
Site entry
Site smoke detector
Site high ambient temperature
Site low ambient temperature
Control equipment cabinet circuit
breaker alarm
RFC 1 circuit breaker and combiner/
multicoupler power supply
6-27