Manual setting of the PID control parameters

It is possible to manually set the PID parameters to any value in the setting range
shown below, to activate a triple value from the predefined standard values described
below (and edit it further if required), or to use the adaption function (self-setting
function) instead of making the settings manually. The LMV5 then acquires the PID
parameters itself.
Parameter:
Proportional band
P-part (Xp) (2...500%)
from 100 °C / 1 bar or 212 °F / 14.5 psi
Reaction:
Xp = 2% ↑ strong / fast
Xp = 500% ↑ weak / slow
Integral action time
I-part (Tn) (0...2,000 s) 0 = no I-part
Reaction:
Tn = 1 ↑ strong / fast
Tn = 2.000 ↑ weak / slow
Derivative action
D-part (Tv) (0...1,000 s) 0 = no D-part
time
Reaction:
Tv = 1 ↑ weak / slow
Tv = 1,000 ↑ strong / fast
The controller's memory contains 5 standard parameter sets.
If required, 1 of these 5 PID triple values can be copied to the storage locations for the
actual values so that it becomes active.
PID standard values for the following applications:
Parameter
Standardparam (Adaption / very fast / fast / normal / slow / very
slow)
Adaption
very fast
(e.g. for small boiler)
fast
normal
slow
very slow
(e.g. for large boiler)
Basic Documentation LMV5...
7 Boiler controller / load controller
The values acquired by the LMV5 adaption function are used
Xp
in %
42.5
14.5
6.4
4.7
3.4
Tn
Tv
in s
in s
68
12
77
14
136
24
250
44
273
48
CC1P7550en