19.13 Technical data

Refer to chapter Technical Data!
Mains voltage X89-01
Safety class
Mains frequency
Power consumption
Degree of protection
Transformer AGG5.210
Primary side
-
Secondary side
-
Transformer AGG5.220
Primary side
-
Secondary side
-
19.14 Loads on terminals, cable lengths and cross-
sectional areas
Refer to chapter Technical Data / LMV5 and AZL5!
Cable lengths / cross-sectional areas
Electrical connection X89
Cable lengths
Cross-sectional areas
Analog inputs:
Fresh air temperature detector
Flue gas temperature detector
QGO20
Interface
Basic Documentation LMV5...
19 O2 trim control with LMV52 and PLL52
AC 120 V
AC 230 V
-15% / +10%
-15% / +10%
I with parts according to II
as per DIN EN 60730-1
50/60 Hz ±6%
Approx. 4 VA
Approx. 4 VA
IP54, housing closed
AC 120 V
AC 12 V (3x)
AC 230 V
AC 12 V (3x)
Screw terminals up to max. 2.5 mm²
'10 m to QGO20
Refer to description of QGO20
Twisted pairs
Pt1000 / LG-Ni1000
Pt1000 / LG-Ni1000
Refer to Data Sheet N7842
Communication bus for LMV52
CC1P7550en
22.05.2018