9.6 Control parameters of the load controller

The control parameters can be defined in 3 different ways.
The memory of the load controller contains 5 standard parameter sets.
Depending on the characteristics of the controlled system, a PID triple value can be
selected and activated.
The following standard parameter sets can be selected:
Xp [%]
very fast
42.5
(e.g. for small boilers)
fast
14.5
normal
6.4
slow
4.7
very slow
3.4
(e.g. for large boilers)
Alternatively, the PID parameters can be directly selected and set within the predefined
value range.
Menu level 3
ControllerParam
With the method of adapting the control parameters, the characteristic data of the
controlled system are acquired with an adaption procedure whereupon matching PID
parameters are calculated.
If possible, the adaption load should be 100%.
Menu level 3
Adaption
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Tn [s]
68
77
136
250
273
Menu level 4
Menu level 5
ContrlParamList
StandardParam
P-Part (Xp)
I_Part (Tn)
D-Part (Tv)
Menu level 4
Menu level 5
StartAdaption
AdaptionLoad
Tv [s]
12
14
24
44
48
Menu level 6
Adaption
very fast
fast
normal
slow
very slow
Menu level 6
185/327
CC1P7550en
22.05.2018