Curve adjustment
Building Technologies

6.6.6 Overload protection

If the actuators block, lockout is enforced.
However, if the actuators cannot reach the positions required by lockout, they would be
damaged due to overtemperatures.
To prevent this, the actuators are deactivated after a maximum time of 35 seconds, or
at 20% above the value parameterized for TmeNoFlame.
Refer to chapter Displays and settings / special function curve adjustment fuel-air ratio
control.
Basic Documentation LMV5...
6 Fuel-air ratio control (FARC)
99/327
CC1P7550en
22.05.2018