22.2.1.8 Basic unit LMV52.4, Software from V04.80 to V10.00

1. New function: Temperature-compensated flue gas recirculation (FGR).
2. Driving to the low-fire positions from phase 50 is adjustable.
3. Extended monitoring of air pressure switch: New mode deactInStby.
When using this setting, the signal of the air pressure switch in standby is not
valued. In case of continuous purging, only start prevention is triggered and a
message appears, in place of a response in the form of shutdown.
4. Extended monitoring of air pressure switch for flue gas recirculation (FGR):
- New mode deactInStby.
When using this setting, the signal of the air pressure switch for flue gas
recirculation (FGR) in standby is not valued. In case of continuous purging, only
start prevention is triggered and a message appears, in place of a response in the
form of shutdown.
- New mode PS VSD.
When using this setting, the pressure switch for flue gas recirculation (FGR) must
deliver an ON signal, if the VSD speed lies above the speed set via parameter
RotSpeed PS on.
If the VSD speed lies below the speed set via parameter RotSpeed PS off, the
pressure switch for flue gas recirculation (FGR) must deliver an OFF signal.

22.2.1.9 Software versions of the 2012/2013 release upgrade

The changeover is expected to take place in Siemens production facilities in autumn
2013:
ASN
LMV50:
V10.20
LMV51 :
V05.10
LMV51.3:
LMV52.2..:
LMV52.4:
Internal LC module:
Internal VSD module:
AZL52:
V05.00
PLL52:
V01.50
Basic Documentation LMV5...
22 Revision history
2012/2013 version release
V05.10
V05.10
V10.20
V02.10
V01.50
307/327
CC1P7550en
22.05.2018