Operational status indication by LED on the actuator:
Reset
150/327
Building Technologies
ON
OFF
ON
EIN
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Figure 76: LED function code
The actuator gives the addressing address via the blinking signal of the LED.
The blink interval is 200 ms.
After each blink cycle, there is a pause of 1.2 seconds.
Example of an actuator for gas
ON
OFF
Figure 77: Addressing completed
This facility makes it possible to reset an addressed actuator in the case of a
replacement, repair, or if addressing is wrong (wrong address assignment by the user).
For that purpose, you need to press the actuator's addressing button for at least 10
seconds when the actuator is in normal operation. The actuator will then reset its
address which is indicated by the LED, which is steady on.
Basic Documentation LMV5...
8 Display and operating unit AZL5
Unaddressed actuator
Auxiliary actuator 1
Auxiliary actuator 2
7550d50en/0118
Air actuator
Gas actuator
Oil actuator
Time
Time
CC1P7550en