4.2.3.14 Startup sequence stop in phase 36

The burner's startup sequence can be stopped in phase 36 via input X5-03 pin 3 if
parameter Config X5-03 has been set to DeaO2/Stp36.
The stop takes place if no mains voltage is present.
Attention!
This function may only be used for non-safety-related multiple burner
applications.
Ι
Note!
At the same time as this parameter setting, input X5-03 pin 2 is set to deactivation of
O2 trim control (DeaO2/Stp36).
This function cannot be used if the inputs (X5-03 pin 2 / pin 3) are being used to
connect an external load controller
(LC_OptgMode = ExtLC X5-03) ↑ invalid parameter setting.
Parameter
Config X5-03 (DeaO2/Stp36)

4.2.3.15 Cooling function in standby mode (only LMV50)

In order to cool the burner in standby mode, a cooling function can be activated using
parameters.
The cooling function is started with a mains voltage signal at input X5-03 pin 3:
The fan is switched on and supervised in the same way as for continuous purging
The actuators used for determining the amount of air are driven to their postpurge
positions
If no mains voltage signal is present, the device behaves as for without continuous
purging in standby mode
Parameter
Config X5-03 (CoolFctStby)
Attention!
This function may only be used for non-safety-related
multiple burner applications.
This means, for example, that the function may not be used for safety-related
purging in plants with several burners in one combustion chamber.
Note!
This function cannot be used if the inputs (X5-03 pin 2 / pin 3) are being used to
connect an external load controller (LC_OptgMode = ExtLC X5-03) ↑ invalid
parameter setting
When using the cooling function, the ContinuousPurge parameter must not be set
to off Sloop or deac/VSD-SL as these settings cancel each other out, potentially
resulting in error messages

4.2.3.16 Long postpurge time (only LMV50 / LMV52.4)

If a long postpurge time is required, an additional time can be set in one-minute
intervals via an additional, non fuel-specific parameter PostpurgeT3long.
This time is added to the two fuel-specific times PostpurgeT3Gas / Oil.
Parameter
PostpurgeT3long
Basic Documentation LMV5...
4 Burner control
CC1P7550en
22.05.2018