6. Selecting the actuator's
direction of rotation
Menu level 1
Menu level 2
Params & Display
Actuators
Ι
168/327
Building Technologies
Menu level 3
DirectionRot
Select the direction of rotation with standard or Reversed.
The standard direction of rotation is counterclockwise when facing the end of the drive
shaft (↑ AZL5).
Note:
To check the direction of rotation, every actuator can be rotated when in the home
position (see item 11).
After setting the curves for the ignition position, the direction of rotation can only be
changed after deleting the curves and the ignition positions in the setting menu
DeleteCurves.
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
Menu level 5
DeleteCurves
1 AirActuator
2 GasActuat(Oil)
3 OilActuator
4 AuxActuator
5 AuxActuator2
6 AuxActuator3
Menu level 6
CC1P7550en
22.05.2018