To create a new curvepoint, select Manual. Set the output of the new point and
acknowledge by pressing Enter.
During the manual action, the actuators travel on the interpolated straight lines between
the curvepoints.
After pressing Enter, each individual actuating device can be selected to optimize the
position.
To leave the curvepoint setting, press the Esc button or store the point by pressing
Enter.
Finally, you can limit the burner output to a minimum and maximum in accordance with
the boiler's requirements.
Menu level 3
GasSettings
Select Autom/Manual/Off and then Burner off.
Menu level 3
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
Menu level 5
LoadLimits
MinLoadGas
MaxLoadGas
Menu level 4
Menu level 5
Menu level 6
Menu level 6
175/327
CC1P7550en
22.05.2018