Repetition Counter - Siemens LMV50 Series Manual

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

64/327
Building Technologies

4.2.3.2 Repetition counter

With heavy oil
Β
With start release
Β
With safety loop
Β
Only LMV50:
With no flame at the
end of safety time
Β
With loss of flame
Β
Number of repetitions = setting value - 1.
That is:
Value = 1: No repetition
Value = 2: Equals 1 repetition
Caution!
Value 16 represents an unlimited number of repetitions!
Basic Documentation LMV5...
4 Burner control
Repetition counter value: Heavy oil direct start
Note:
Changes only become active after a reset (power on / reset)
Repetition limit value: Start prevention
Note:
Changes only become active after a reset (power on / reset)
Repetition limit value: Safety loop
Note:
Changes only become active after a reset (power on / reset)
Repetition limited value: No flame at the end of first safety time
Setting choices for gas and oil together:
1...3 ⇓ none...2 repetitions
Note!
Changes only become active after a reset (power on / reset)
Caution!
Setting only in accordance with the relevant application
standard.
Repetition limit value: Loss of flame
Note!
Changes only become active after a reset (power on / reset).
Caution!
Setting only in accordance with the relevant application
standard.
CC1P7550en
22.05.2018