Fuel Meter Readings - Siemens LMV50 Series Manual

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

246/327
Building Technologies

18.1.7 Fuel meter readings

The VSD module ascertains the cumulated gas or oil throughout. For each type of fuel,
there is 1 resettable and 1 nonresettable meter available.
When resetting the fuel meters, the reset date is stored.
The system continuously calculates the throughput of the selected type of fuel. The
calculation time is dynamic and reaches from 1 to 10 seconds.
If the meter delivers no pulse for 10 seconds, the throughput displayed is «0». This
means that with minimum throughput, the sensor's pulse frequency should be a minimum
of 0.1 Hz.
The display is smoothed.
The maximum frequency is 300 Hz when fuel throughput is at its maximum.
Parameter
Volume Gas
Volume Oil
Volume Gas R
Volume Oil R
Reset DateGas
Reset DateOil
Curr Flow Rate
Basic Documentation LMV5...
18 VSD module
CC1P7550en
22.05.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents