Operating status monitoring
Output current
Group
LED Display
Drive group
Inverter output current can be monitored in Cur.
Motor RPM
Group
LED Display
Drive group
Function
group 2
Motor rpm can be monitored in rPM.
When H40 is set to 0 {V/F control} or 1 {PID control}, the Inverter output frequency (f) is displayed in
RPM using the formula below. Motor slip is not considered.
H31 : Enter the number of rated motor poles on the nameplate.
H74 : This parameter is used to change the motor speed display to rotating speed
(r/min) or mechanical speed (m/mi).
Inverter DC Link Voltage
Group
LED Display
Drive group
dCL
Inverter DC link voltage can be monitored in dCL.
It is the voltage detected between P1 and N terminal of power terminal.
Description
CUr
Output current
Description
rPM
[Motor RPM]
[Number of motor poles]
H31
H40
[Control mode select]
H74
[Gain for Motor rpm display]
×
120
=
RPM
H
31
Parameter Name
[Inverter DC Link Voltage]
2
times the value of input voltage is displayed while motor is at a stop.
Set
value
-
Set
value
-
-
-
-
f
H
74
×
100
Set
value
-
11-1
11. Monitoring
Min/Max
Factory
range
default
Min/Max
Factory
range
default
2/12
4
0/2
0
1/1000
100