LG SV-iC5 Series Instruction Manual page 48

Lg inverter instructions manual
Hide thumbs Also See for SV-iC5 Series:
Table of Contents

Advertisement

7. Function list
LED
Parameter
display
name
F51
[Electronic
4)
thermal level
for 1 minute]
F52
[Electronic
thermal level
for continuous]
F53
[Motor cooling
method]
F54
[Overload
warning level]
F55
[Overload
warning time]
F56
[Overload trip
select]
F57
[Overload trip
level]
F58
[Overload trip
time]
4): Set F50 to 1 to display this parameter
Min/Max
range
50/200
This parameter sets max current capable
[%]
of flowing to the motor continuously for 1
minute.
The set value is the percentage of H33 –
[Motor rated current].
It cannot be set below F52 –[Electronic
thermal level for continuous].
50/150
This parameter sets the amount of current
[%]
to keep the motor running continuously.
It cannot be set higher than F51 –
[Electronic thermal level for 1 minute].
0/1
0
Standard motor having cooling fan
directly connected to the shaft
1
A motor using a separate motor to
power a cooling fan.
30/150
This parameter sets the amount of current
[%]
to issue an alarm signal at a relay or multi-
function output terminal (see I54, I55).
The set value is the percentage of H33-
[Motor rated current].
0/30 [sec]
This parameter issues an alarm signal
when the current greater than F54- [Overload
warning level] flows to the motor for F55-
[Overload warning time].
0/1
This parameter turns off the inverter output
when motor is overloaded.
30/200
This parameter sets the amount of
[%]
overload current.
The value is the percentage of H33-
[Motor rated current].
0/60 [sec]
This parameter turns off the inverter output
when the F57- [Overload trip level] of current
flows to the motor for F58- [Overload trip
time].
Description
7-6
Function group 1
Factory
Adjustable
defaults
during run
150
0
100
0
0
0
150
0
10
0
1
0
180
0
60
0
SV-iC5
Page
12-1
12-2
12-3