LG SV-iC5 Series Instruction Manual page 46

Lg inverter instructions manual
Hide thumbs Also See for SV-iC5 Series:
Table of Contents

Advertisement

7. Function list
LED
Parameter
display
name
F20
[Jog
frequency]
F21
[Max
frequency]
F22
[Base
frequency]
F23
[Start
frequency]
F24
[Frequency
high/low limit
select]
F25
[Frequency
2)
high limit]
F26
[Frequency low
limit]
F27
[Torque Boost
select]
F28
[Torque boost
in forward
direction]
Min/Max
range
0/400
This parameter sets the frequency for Jog
[Hz]
operation.
It cannot be set above F21 – [Max
frequency].
40/400 *
This parameter sets the highest frequency
[Hz]
the inverter can output.
It is frequency reference for Accel/Decel
(See H70)
If H40 is set to 3(Sensorless vector), it can
be settable up to 300Hz *.
☞ Caution : Any frequency cannot be set
above Max frequency.
30/400
The inverter outputs its rated voltage to
[Hz]
the motor at this frequency (see motor
nameplate). In case of using a 50Hz motor,
set this to 50Hz.
0/10
The inverter starts to output its voltage at
[Hz]
this frequency.
It is the frequency low limit.
0/1
This parameter sets high and low limit of
run frequency.
0/400
This parameter sets high limit of the run
[Hz]
frequency.
It cannot be set above F21 – [Max
frequency].
0/400
This parameter sets low limit of the run
[Hz]
frequency.
It cannot be set above F25 - [Frequency
high limit] and below F23 – [Start frequency].
0/1
0
Manual torque boost
1
Auto torque boost
0/15 [%]
This parameter sets the amount of torque
boost applied to a motor during forward run.
It is set in percent of Max output voltage.
Description
7-4
Function group 1
Factory
Adjustable
defaults
during run
10.0
O
60.0
X
60.0
X
0.5
X
0
X
60.0
X
0.5
X
0
X
5
X
SV-iC5
Page
10-3
9-19
9-15
9-19
9-19
9-17
9-17

Hide quick links:

Advertisement

Table of Contents
loading