LG SV-iC5 Series Instruction Manual page 53

Lg inverter instructions manual
Hide thumbs Also See for SV-iC5 Series:
Table of Contents

Advertisement

LED
Parameter
display
Name
H26
[Number of
Auto Restart
try]
H27
[Auto Restart
time]
H30
[Motor type
select]
H31
[Number of
motor poles]
H32
[Rated slip
frequency]
H33
[Motor rated
current]
H34
[No Load
Motor
Current]
H36
[Motor
efficiency]
Min/Max
Range
0/10
This parameter sets the number of
restart tries after a fault occurs.
Auto Restart is deactivated if the fault
outnumbers the restart tries.
This function is active when [drv] is set
to 1 or 2 {Run/Stop via control terminal}.
Deactivated during active protection
function (OHT, LVT, EXT, HWT etc.)
0/60 [sec]
This parameter sets the time between
restart tries.
0.2/2.2
0.2
0.4
0.75
1.5
2.2
2/12
This setting is displayed via rPM in
drive group.
0/10
=
f
f
s
r
[Hz]
f
Where,
s
= Rated slip frequency
f
r
rpm
P
1.0/20
Enter motor rated current on the
[A]
nameplate.
0.1/12
Enter the current value detected when
[A]
the motor is rotating in rated rpm after the
load connected to the motor shaft is
removed.
Enter the 50% of the rated current
value when it is difficult to measure H34 -
[No Load Motor Current].
50/100
Enter the motor efficiency (see motor
[%]
nameplate).
Description
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
×
rpm
P
120
= Rated frequency
= Motor nameplate RPM
= Number of Motor poles
7-11
7. Function list
Function group 2
Factory
Adjustable
defaults
during run
0
O
1.0
O
-
X
1)
Automatically
set
-
X
-
X
2)
Automatically
set
-
X
-
X
-
X
SV-iC5
Page
10-
15
10-6
10-6

Hide quick links:

Advertisement

Table of Contents
loading