FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Step 2 Open the electric control box, turn off the active power switch QF1 and standby
power switch QF2, and remove the air filter in the middle.
Step 3 Remove the cable terminals from the T/H sensor.
Step 4 Pull out the T/H sensor upwards.
Figure 10-4 Replacing the T/H sensor
Before installing the new T/H sensor, ensure that its DIP switch setting is consistent with that on
the original T/H sensor. That is, the first toggle switch is ON, and the others are OFF.
Step 5 Install the new T/H sensor at the original position, and connect the cable
terminals to the T/H sensor.
Step 6 Install the air filter.
Step 7 Power on the device.
Step 8 Tap Start on the home screen.
----End
10.5 (Optional) Replacing an Electric Heater
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Turn off the general switch. For a unit that has two power inputs, turn off the
active power switch QF1 and standby power switch QF2.
Issue 05 (2022-12-15)
NO TE
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement
123