Huawei FusionCol8000-C210 User Manual page 169

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
NO TE
● You are advised to use channel steel or angle steel to prepare a base. The thickness of the angle steel must
be greater than 4 mm. The width of the channel steel must be greater than 60 mm. If other types of steel
are used, the steel width must match the rack mounting holes.
● The distance between the base and the side is 35 mm, and that between the bolts fixing the cabinet and the
side is 51.2 mm. If you cannot directly drill holes on the base to weld nuts, you can follow the preceding
figure. Alternatively, you can weld the nuts on L-shaped or other components, and then fix the nuts on the
base.
● The recommended minimum height of the base is 250 mm.
● The bearing capacity of the base must be at least 2 tons.
● Welding errors must be under control during the welding. Otherwise, the base may be unusable.
● If an air baffle needs to be added to the base, drill holes on the base to secure the air baffle.
Issue 05 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
B Base Dimensions
161

Advertisement

Table of Contents
loading

Table of Contents