FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
3.2 Operating Environment Specifications
Environmental Specifications
Table 3-2 Environmental specifications
Operating
temperature
Operating humidity
Storage temperature
Storage humidity
Inlet water
temperature
Altitude
Temperature
adjustment precision
Humidity adjustment
precision
External residual
pressure
Figure 3-1 Cooling capacity derating coefficient curve in proportion to the altitude
Issue 05 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
4–45°C
20%–80% RH
–40°C to +70°C
5%–95% RH (non-condensing)
15–20°C
0–4000 m (derated when the altitude is in the range
of 1000–4000 m)
±1°C
±5% RH
0–300 Pa
3 Product Specifications