Prerequisites
If micro differential pressure sensors are installed, perform the following
operations accordingly. If micro differential pressure sensors are not installed, skip
this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, and set
Air-side differential pressure sensor type to 0~500 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Parameter
Indoor fan control
type
Indoor fan pressure
difference setpoint
Air-side differential
pressure sensor type
Min indoor fan speed
Max indoor fan speed
----End

5.5.3 (Optional) Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Issue 05 (2022-12-15)
Teamwork group No.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork control groups can be set (1–4).
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
● R/S air temp diff prop ctrl: controls the indoor fan
speed based on the proportion of temperature
difference between return air and supply air.
● R/S air temp diff ctrl: controls the indoor fan speed
based on the temperature difference between return
air and supply air.
● Pressure diff ctrl: controls the indoor fan speed
based on the pressure difference.
Specifies the control value of indoor fan pressure
difference.
NOTE
This parameter is displayed when Indoor fan control type is
set to Pressure diff ctrl.
Select the proper differential pressure sensor type
based on the measurement range of the differential
pressure sensor.
Specifies the minimum rotational speed of the indoor
fan.
Specifies the maximum rotational speed of the indoor
fan.