FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual

5.5 Initial Configuration

5.5.1 Setting T/H Sensor Parameters

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Figure 5-5 Setting humidity and temperature
Issue 05 (2022-12-15)
Sets and checks teamwork control information based on the requirements of
the smart cooling product.
Running
Checks the component status, system parameters, and the name, control and
operating status, and other related information of the components in the
current smart cooling product system.
Alarms
Checks the active and historical alarms of the smart cooling product, and
blink function.
Settings
Sets the involved parameters for the operation of the smart cooling product.
Maint
Checks or deletes the logs or component total runtime/run factor, manually
diagnoses each component, calibrates the sensor, exports data, and upgrades
the system.
About
Checks the model, manufacturer, monitoring version, detail version
information, and electronic label of the display module.
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip
If you need to enable a humidity and temperature sensor, log in as the admin
user.
This section describes how to enable Return air sensor 2.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Step
2.
5 Power-On Commissioning
81