5.5.4.3 Setting Communications Parameters (SNMP Protocol)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
Figure 5-10 Setting SNMP communication parameters
Issue 05 (2022-12-15)
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section which will be needed when you
access a smart cooling product to an NMS.
One smart cooling product supports concurrent access of up to 6 NMSs
through SNMP.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Enter the actual IP address of the NMS. The IP
addresses of the display board, client NMS, and server
NMS must be unique.
This parameter is configurable when Link mode
involves Client.
This parameter is configurable when Link mode
involves Client.
● Connecting to the NetEco: Set this parameter to
32907 if Client encryption is enabled, or set it to
32906 if Client encryption is disabled.
● Connecting to other NMSs: You are advised not to
change the value. In special cases, set this
parameter based on the site requirements.
Secondary authentication password used for Modbus-
TCP connection.
5 Power-On Commissioning