FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Prerequisites
●
●
●
Procedure
Step 1 Tap Shutdown on the home screen of the display module. Turn off the active
power switch QF1, standby power switch QF2 (for models with a single power
supply, there is no need to switch on QF2), and drive switch QF3.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Remove the air filter.
Step 3 Remove the liquid level detector.
Figure 10-14 Removing a liquid level detector
Step 4 Remove the low liquid level sensor and the wiring terminal.
Issue 05 (2022-12-15)
A liquid level detector needs to be replaced.
A spare liquid level detector of the same model is available and functional.
Tool: Phillips screwdriver
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement
132