Context
● This section describes how to replace a PSU. Refer to this section if you need to
replace the main control module.
● The new PSU must be installed in the same slot of the faulty PSU. Otherwise,
the smart cooling product may fail to work properly.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Remove the air filter in the middle and push down the clip of the PSU.
Figure 10-12 Removing a PSU
Step 3 Take out the handle and directly pull out the PSU from the subrack.
Step 4 Insert the spare PSU into the corresponding slot of the power distribution subrack,
and push the clip downwards to lock the PSU.
Step 5 Install the air filter in the middle.
Step 6 Tap Start on the home screen.
----End

10.10 Replacing an Inlet Solenoid Valve