Huawei FusionCol8000-C210 User Manual page 135

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:
Table of Contents

Advertisement

FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Step 2 Open the electric control box, and turn off the active power switch QF1 and
standby power switch QF2.
Step 3 Remove the fan guard.
Step 4 Cut off the cable ties that bind the cable connected to the faulty fan, and remove
the fan terminal.
Step 5 Remove the auxiliary fixture for installing the fan at the bottom of the electric
control box.
Figure 10-8 Auxiliary fixture position
(1) Electric control box
Step 6 Install the auxiliary fixtures on the fan support using four M6x16 bolts (standard
configuration), as shown by (2) in the following figure. Remove the screws that
secure the fan support to the equipment frame.
Issue 05 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement
(2) Auxiliary fixture
127