FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Locati
on
Cold
aisle
Hot
aisle
● The default T/H sensor address is 1.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
Issue 05 (2022-12-15)
Display
Ad
Name
dre
ss
Cold aisle
11
T/H
sensor 1
Cold aisle
12
T/H
sensor 2
Cold aisle
13
T/H
sensor 3
Cold aisle
14
T/H
sensor 4
Cold aisle
15
T/H
sensor 5
Hot aisle
21
T/H
sensor 1
Hot aisle
22
T/H
sensor 2
Hot aisle
23
T/H
sensor 3
Hot aisle
24
T/H
sensor 4
Hot aisle
25
T/H
sensor 5
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
DIP Switch Sequence No.
1
2
3
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
4 System Installation
4
5
6
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
68