Recommended ferrule
For safe wiring and reliability, it is recommended to use following ferrules.
When you use an option mounted, please use a rod terminal without sleeve to wire so that to
avoid hitting the option case.
Rod terminal with sleeve
Wire size
Model name of
2
mm
(AWG)
0.25 (24)
AI 0.25-8YE
0.34 (22)
AI 0.34-8TQ
0.5 (20)
AI 0.5-8WH
0.75 (18)
AI 0.75-8GY
Rod terminal without sleeve
Wire size
Model name of
2
mm
(AWG)
0.5 (20)
A 0,5-8
0.75 (18)
A 0,75-8
* Supplier: Phoenix contact
Crimping pliers: CRIMPFOX 6 (CRIMPFOX UD 6-4 or CRIMPFOX ZA 3)
How to connect?
(1) Push down an orange actuating lever by a slotted screwdriver (width 2.5mm max.).
(2) Plug in the conductor.
(3) Pull out the screwdriver then the conductor is fixed.
2.5mm
L1
ferrule *
[mm]
8
8
8
8
L1
ferrule *
[mm]
7.3
7.3
L2
[mm]
12.5
12.5
14
14
L2
[mm]
8
8
Push down an
orange actuating
lever.
24
Φd
ΦD
[mm]
[mm]
0.8
2.0
0.8
2.0
1.1
2.5
1.3
2.8
Φd
ΦD
[mm]
[mm]
1.0
2.1
1.2
2.3
Plug in the
Pull out the
conductor.
screwdriver to fix
the conductor.

Advertisement