Download Print this page

Hitachi WJ200 Series Quick Reference Manual page 90

Hide thumbs Also See for WJ200 Series:

Advertisement

Expansion Card Functions
NOTE: Marking [  ],[  ],[
 : Configuration changes are possible during operation.
: You cannot change the parameters during operation.
*
1: In case of (b031) soft lock selections"10", parameter changing during operation is
possible.
"P" parameters will be appeared when the expansion option is connected.
F u n c .
N a m e
C o d e
P001
Reaction when option card
error occurs
[EA] terminal selection
P003
Pulse train input mode
P004
selection for feedback
Encoder pulse setting
P011
P012
Simple positioning selection
P014
Creep pulse ratio
P015
Creep Speed
Positioning completion range
P017
Over-speed error detection
P026
level
P027
Speed deviation error
detection level
Acceleration/Deceleration
P031
setting source selection
P033
Torque command input
selection
P034
Torque command level input
P036
Torque bias mode selection
Torque bias value setting
P037
*
1 ],in the table show following meaning.
" P " F u n c t i o n
D e s c r i p t i o n
Two option codes:
00...Inverter trips
01...Ignores the error (Inverter
continues operation)
Three option codes:
00...Speed reference (incl. PID)
01...For control with encoder
feedback
02...Extended terminal for EzSQ
Four option codes:
00...Single-phase pulse [EA]
01...2-phase pulse (90 difference) 1
([EA] and [EB])
02...2-phase pulse (90 difference) 2
([EA] and [EB])
03...Single-phase pulse [EA] and
direction signal [EB]
Sets the pulse number (ppr) of the
encoder, set range is 32 to1024
pulses
Two option codes:
00...simple positioning deactivated
01...simple positioning activated
0.0 to 400.0[%]
Set range is start frequency (b082)
to 10.00 Hz
0 to 10000 [pulse]
Set range is 0.0 to 150.0%
Set range is 0.00 to 120.00 Hz
00...Operator, 03...EzSQ
Four option codes:
00...Analog voltage input [O]
01...Analog current input [OI]
03...Operator, 06...Option
Set range is 0 to 200%
Three option codes:
00...No bias
01...Operator
05...Option
Range is –200 to 200%
84
D e f a u l ts
R u n
M o d e
I n i t i a l
Units
E d i t
d a ta
*
00
1
00
00
512.
00
125.0
%
*
5.00
1
Hz
50
Pulse
*
115.0
1
%
*
10.00
1
Hz
00
00
0.
%
00
0.
%
-
-
-
-
-
-
-
-

Advertisement

loading