F u n c .
N a m e
C o d e
b008
Restart mode on over voltage /
over current trip
Number of retry on over
b010
voltage / over current trip
b011
Retry wait time on over voltage
/ over current trip
b012
Level of electronic thermal
Level of electronic thermal,
b212
nd
2
motor
b013
Electronic thermal
characteristic
b213
Electronic thermal
characteristic, 2
Free setting electronic thermal
b015
~freq.1
b016
Free setting electronic thermal
~current1
Free setting electronic thermal
b017
~freq.2
b018
Free setting electronic thermal
~current2
b019
Free setting electronic thermal
~freq.3
Free setting electronic thermal
b020
~current3
b021
Overload restriction operation
mode
Overload restriction operation
b221
nd
mode, 2
motor
Overload restriction level
b022
Overload restriction level,
b222
nd
2
motor
" b " F u n c t i o n
Select inverter restart method,
Five option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz
02Resume operation after
frequency matching
03Resume previous freq. after
active freq. matching, then
decelerate to stop and display
trip info
04Resume operation after active
freq. matching
Range is 1 to 3 times
Range is 0.3 to 100 s.
Set a level between 20% and 100%
for the rated inverter current.
Select from three curves, option
codes:
00Reduced torque
nd
motor
01Constant torque
02Free setting
Range is 0 to 400Hz
Range is 0 to inverter rated current
Amps
Range is 0 to 400Hz
Range is 0 to inverter rated current
Amps
Range is 0 to 400Hz
Range is 0 to inverter rated current
Amps
Select the operation mode during
overload conditions, four options,
option codes:
00Disabled
01Enabled for acceleration and
constant speed
02Enabled for constant speed
only
03Enabled for acceleration and
constant speed, increase speed
at regeneration.
Sets the level of overload restriction,
between 20% and 200% of the rated
current of the inverter, setting
resolution is 1% of rated current
D e s c r i p t i o n
60
Run
D e f a u l ts
Mode
I n i t i a l
U n i ts
Edit
d a ta
*
1
00
*
1
3
times
*
1
1.0
s
Rated
*
1
A
current for
each
*
1
A
inverter
model
*
1
01
*
1
01
*
1
0.0
Hz
*
1
0.00
Amps
*
1
0.0
Hz
*
1
0.00
Amps
*
1
0.0
Hz
*
1
0.00
Amps
*
1
01
*
1
01
Rated
*
current
1
Amps
x 1.5
Rated
*
current
1
Amps
x 1.5