F u n c .
N a m e
C o d e
C071
Communication speed
C072
Modbus address
Communication parity
C074
Communication stop bit
C075
C076
Communication error
select
C077
Communication error
time-out
C078
Communication wait time
O input span calibration
C081
C082
OI input span calibration
C085
Thermistor input (PTC)
span calibration
C091
Debug mode enable
Communication selection
C096
C098
EzCOM start adr. of master
C099
EzCOM end adr. of master
C100
EzCOM starting trigger
" C " F u n c t i o n
D e s c r i p t i o n
Eight option codes:
032,400 bps
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
0857,600 bps
0976,800 bps
10115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
00No parity
01Even parity
02Odd parity
Two option codes:
11 bit
22 bit
Selects inverter response to
communications error.
Five options:
00Trip
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerates to a stop
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 s.
0.0 = disabled
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms.
Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
Scale factor between the external
frequency command on terminals
L–OI (currnt input) and the
frequency output,
range is 0.0 to 200%
Scale factor of PTC input.
Range is 0.0 to 200%
Factory use only.
Do not change.
00Modbus-RTU
01 EzCOM
02 EzCOM<administrator>
1. to 8.
1. to 8.
00 Input terminal
01 Always
71
D e f a u l ts
Run
Mode
I n i t i a l
Edit
d a ta
*
1
05
*
1
1.
*
1
00
*
1
1
*
1
02
*
1
0.00
*
1
0.
100.0
100.0
100.0
00
1.
1.
00
U n i ts
baud
bit
s
ms
%
%
%