F u n c .
N a m e
C o d e
A041
Torque boost select
Torque boost select, 2
A241
Manual torque boost value
A042
A242
Manual torque boost value, 2
motor
A043
Manual torque boost
frequency
A243
Manual torque boost
frequency,
nd
2
motor
V/f characteristic curve
A044
A244
V/f characteristic curve,
nd
2
motor
A045
V/f gain
nd
A245
V/f gain, 2
motor
Voltage compensation gain for
A046
automatic torque boost
Voltage compensation gain for
A246
automatic torque boost,
motor
A047
Slip compensation gain for
automatic torque boost
A247
Slip compensation gain for
automatic torque boost,
motor
DC braking enable
A051
DC braking frequency
A052
DC braking wait time
A053
A054
DC braking force for
deceleration
" A" F u n c t i o n
D e s c r i p t i o n
Two options:
00Manual torque boost
01Automatic torque boost
nd
motor
Can boost starting torque
between 0 and 20% above
normal V/f curve,
nd
range is 0.0 to 20.0%
Sets the frequency of the V/f
breakpoint for torque boost,
range is 0.0 to 50.0%
Four available V/f curves;
00Constant torque
01Reduced torque (1.7)
02Free V/F
03*Sensorless vector (SLV)
*Only CT mode
Sets voltage gain of the inverter,
range is 20. to 100.%
Sets voltage compensation gain
under automatic torque boost,
range is 0. to 255.
nd
2
Sets slip compensation gain
under automatic torque boost,
range is 0. to 255.
nd
2
Three options; select codes:
00Disable
01Enable during stop
02Frequency detection
The frequency at which DC
braking begins,
range is from the start frequency
(b082) to 60Hz
The delay from the end of
controlled deceleration to start of
DC braking (motor free runs until
DC braking begins),
range is 0.0 to 5.0 sec.
Level of DC braking force,
settable from 0 to 100%
53
D e f a u l ts
Run
Mode
I n i t i a l
U n i ts
Edit
d a ta
00
00
1.0
1.0
5.0
5.0
00
00
100.
100.
100.
100.
100.
100.
*
1
00
*
0.5
1
*
1
0.0
*
1
50.
%
%
%
%
%
%
Hz
s
%