E3/Eh 03 / F5/Ec 07 (Fan Speed Outside Of The Normal Range Diagnosis And Solution) - Pioneer QUANTUM INVERTER Series Service & Troubleshooting Manual

Hide thumbs Also See for QUANTUM INVERTER Series:
Table of Contents

Advertisement

7.4
E3/EH 03 / F5/EC 07 (Fan speed is operating outside of normal range diagnosis and
solution)
Description: When indoor / outdoor fan speed keeps too low or too high for a certain time, the LED displays the
failure code and the AC turns off.
Recommended parts to prepare:
• Connection wires
• Fan assembly
• Fan motor
• PCB
Troubleshooting and repair:
Power off, then restart the unit after 2 minutes.
Shut off the power supply,
Check the wiring of fan motor.
the fan motor from the PCB.
Is it within normal parameters?
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Does a problem remain?
YES
rotate the fan by hand.
Does it turn easily?
YES
Is it improperly wired?
YES
Measure the voltage for
YES
Replace the fan motor
Troubleshooting
NO
The unit is operating normally
NO
Find the cause of the problem and resolve it
Ensure proper connections
NO
Replace the main PCB