Pioneer QUANTUM INVERTER Series Service & Troubleshooting Manual page 39

Hide thumbs Also See for QUANTUM INVERTER Series:
Table of Contents

Advertisement

parameter of EEPROM. Its value ranges from -6°C to 6°C.
• When T1-Ts>-ΔT3, the compressor ceases operation.
• When T1-Ts<-ΔT3-1.5°C (2.7 °F), the compressor
continues operation.
• When the AC is operating in mute mode, the
compressor operates at a low frequency.
• When the current exceeds the preset value, the current
protection function activates and the compressor
ceases operation.
3.5.2
Indoor Fan Control:
• When the compressor is on, the indoor fan speed can
be set to high, medium, low, or auto. And the anti-
cold wind function has the priority.
• Anti-cold air function
• The indoor fan is controlled by the indoor
temperature T1 and indoor unit coil temperature
T2.
T2
TEL0+23- TE1
TEL0+21- TE1
TEL0+19- TE1
TEL0+17- TE1
TEL0+15- TE1
TEL0+13- TE1
T1 ≥ 19°C(66.2 °F)
15 °C(59°F) ≤ T1 ≤ 18 °C(64.4°F)
T1<15 °C(59°F)
• When the indoor temperature T1 reaches the setting
temperature, the compressor continues operation,
the indoor fan motor runs at the minimum speed or
setting speed.(The anti-cold air function is valid).
• The indoor fan is controlled as below:
Setting fan
T1-Td °C(°F)
speed
H
M
L
• Auto fan action in heating mode:
Setting fan speed
TEL0+18- TE1
H
TEL0+16- TE1
M+
TEL0+14- TE1
M
TEL0+12- TE1
L
TEL0+10- TE1
Super slow
TEL0
Fan off
ΔTE1=0
ΔTE1=19°C-T1
(34.2 °F-T1)
ΔTE1=4 °C(7.2 °F)
Actual fan speed
H- (H-=H-G)
H (=H)
H+(H+=H+G)
M-(M-=M-Z)
M(M=M)
M+(M+=M+Z)
L-(L-=L-D)
L(L=L)
L+(L+=L+D)
Product Features
3.5.3
Outdoor Fan Control:
Case 1:
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency .
• For different outdoor units, the fan speeds are
different.
Case 2:
• The outdoor unit will be run at different fan speed
according to T4.
• For different outdoor units, the fan speeds are
different.
3.5.4
Defrosting mode
Case 1:
• The unit enters defrosting mode according to the
temperature value of T3 and T4 as well as the
compressor running time.
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the "
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
T3 rises above TCDE1.
• T3 maintained above TCDE2 for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting
mode.
Case 2:
• The unit enters defrosting mode according to the
temperature value of T3 as well as the compressor
running time.
-
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the "
6
T1-Td
" symbol is displayed.
" symbol is displayed.