Resistance Value
KSK103D33UEZ3
Blue-Red
Blue-Black
Red-Black
Reference Table for Outdoor Condensing Unit Compressor Models
YN009AMFI22RPE YN009GMFI22RPE
KSK103D33UEZ3
YN012AMFI22RPE YN012GMFI22RPE
YN009AMFI20RPD
YN012AMFI20RPD YN012GMFI20RPD
KSN98D64UFZ3
KSN140D21UFZ
KTM240D43UKT
YN024GMFI20RPD
KTF250D22UMT
YN030GMFI20RPD YN036GMFI20RPD
KSN140D58UFZ
Use the above compressor values to confirm proper resistance values between compressor windings.
The integrity of the compressor should also be examined by testing each winding individually to ground.
These should read 0 or OL (Open Line) to confirm the compressor has continuity and not been grounded.
Note: The picture and the value are only for reference, actual condition and specific value may vary.
KSN98D64UFZ3
2.13Ω
2.75Ω
YN009GMFI20RPD
YN018GMFI20RPD
YN024GMFI22RPE
YN018GMFI22RPD