Restart Interlock - Siemens SIMATIC FS600 Instruction Manual

Table of Contents

Advertisement

SAFETY NOTES
Automatic startup / restart must only be used in cases where there is absolutely no
possibility that the effective detection zone could be entered or bypassed in some other
way. Depending on the hazard assessment, visual and / or acoustic startup warnings
should be provided.
If parameters are set for the function "Manual restart", the required enable from the
startup/restart button affects all detection zones and is independent of any detection
zone changeover. If the current detection zone is manually enabled, this enable also
applies even if the system switches to another detection zone and this detection zone
becomes free! If startup/restart interlock is in effect in the current detection zone, it is
also in effect for the other detection zone to which the system switches even if this
detection zone is free.
5.4.7

Restart Interlock

The SIMATIC FS600 Laser Scanner is equipped with a restart interlock function. You
can select or deselect this function as needed to connected restarting of the machine to
a manual approval. It affects all detection zones and does not depend on any detection
zone changeovers. For information on how to configure the scanner appropriately,
please refer to SIMATIC FS600 Parameterization Software LS4soft (Section: "Safety-
relevant parameters" folder)
The restart button must be mounted so that
the entire danger zone (or detection zone area ) can be viewed from the operating
position.
it is not possible to directly step or reach into the danger zone or danger point from
the operating position.
The button refer to the areas to be enabled in a easily understandable manner.
Please comply with the safety notes in Chapter 3 and 5.4.6.