Connecting The Simatic Fs600 Laser Scanner To A Safety Sequence Circuit With Manual Restart, Relay Monitoring, Without Zone Pair Changeover - Siemens SIMATIC FS600 Instruction Manual

Table of Contents

Advertisement

8.2
Connecting the SIMATIC FS600 Laser Scanner to a Safety Sequence
Circuit with Manual Restart, Relay Monitoring, without Zone Pair
Changeover
a
b
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
SIMATIC FS600 Laser Scanner
a
= Fuse 1.25 A, semi time-lag
b
= Restart button
c
= Fuse 4 A, delay-action
d
= Fuse 1 A, delay-action
Fig. 8.2-1:
In this example, the relay monitoring is performed by an external safety module (e.g.
MSI-SR2/F). Relays K4 and K5 must be equipped with positively guided contacts. A
suitable mechanism must be provided for extinguishing sparks. Please note that doing
this will cause the switching time to be extended.
Please refer to the operating instructions for the components.
Channels "x" and "y" must be integrated for Category 3 in accordance with DIN EN 954-1.
Integrating one channel based on "z" is only permitted with a one-channel control system
and taking into consideration the results of a risk analysis.
Serial machine controls are admissible only insofar the valid regulations allow.
K5
K4
S35 S34
Wiring the SIMATIC FS600 Laser Scanner with external restart interlock
and relay monitoring, and without zone pair changeover
K4
K5
S31S1214
24
S21S22
SIMATIC FS400
Auswertegerät 3RG7847
x
K4
x
+24 V
GND
PE
c
c
d
13 23
A2 A1
y
z
K5
K4
y
K5
z
71